Malfunctions of gas boilers Proterm and their elimination

Home »Classification of gas boilers» Principles of operation »Setting up gas boilers Proterm

cauldron wipe cheetah

Gas boilers Proterm are popular with consumers due to their reliability, European quality and reasonable price. Among floor devices, the Bear series is known, and among wall devices, the Cheetah is considered the most versatile line. Models with the letter designation MOV are equipped with an open combustion chamber and MTV are equipped with a closed one. Consider how to set up Proterm gas boilers.

  • 1 Heating modes Proterm Cheetah
  • 2 How does Proterm Cheetah work when connecting thermostats?
  • 3 Setting up the gas boiler Proterm Medved

Heating modes Proterm Cheetah

The gas boiler Proterm Cheetah can operate in several modes:

  1. "Heating" - press the MODE button once, and the display will show the "radiator" symbol with the current pressure value in the heating system. While in this mode, the unit works only for the production of heating, while DHW is turned off.
  2. "Summer" - activated by pressing MODE twice. The display will show the pressure in the heating system together with the symbol "tap with a drop of water". In this mode, the boiler operates only for hot water supply.
  3. "Vacation" - press the MODE button three times, and the OFF symbol appears on the screen with the pressure reading. In this mode, heating and domestic hot water does not work, but all protective functions of the device are active.

control panel proterm cheetah

The desired heating or hot water temperature can be adjusted using the "+" and "-" buttons. The setting is carried out as follows:

  1. The DHW temperature is regulated as follows: after pressing the "+" or "-" button, the symbol "tap with a drop of water" and "ºC" start blinking. The required temperature value is set in the range from 38ºC to 60ºC.
  2. The heating temperature is also set using the "+" and "-" keys. After pressing one of them, click on the MODE button, a blinking symbol "radiator" and "ºC" appears. Then, using the "+" and "-" keys, set the optimal value of the heat carrier in the range of 38-85ºC.

setting proterm cheetah

The operation of the gas boiler Proterm Cheetah without thermostats is not very economical. It is recommended to purchase a room thermostat for maximum savings.


documents that are relevant to this issue. Issue ...

Page 20

  • Picture
  • Text

18

documents that are relevant to this issue. By fulfilling the requirements listed in the standards, you can avoid such undesirable phenomena as excessive cooling of combustion products, penetration of moisture into the masonry, fluctuations in the chimney draft, and, thereby, their negative impact on the operation of the boiler.

The combustion air enters the boiler from the room in which it is installed. Ensure that a sufficient amount of combustion air flows into the room - about 11 m

3

air for 1 m

3

natural gas.

The boiler is installed in a frost-protected room near the chimney. The permissible ambient temperature for the operation of the boiler is from + 3C to + 45C.

The combustion air supplied to the apparatus must be technically free of chemicals that may contain, for example, fluorine, chlorine or sulfur. Sprays, paints, solvents, cleaning agents and adhesives contain substances of a kind that can cause corrosion during operation of the appliance under unfavorable conditions, including in the chimney system. The combustion air must not contain mechanical impurities, for example: construction dust, sand, etc.

For the removal of combustion products of boilers PROTHERM 20, 30, 40, 50 KLZ, you can use the additional device "PROTHERM PT 20 (30, 40, 50) SEMITURBO" extension, which provides forced removal of combustion products.

The device makes it possible to operate cast iron boilers in cases where it is not possible to use the normal removal of combustion products into the chimney. The extension is connected to the boiler outlet to connect the chimney. The outlet of the combustion products of the extension allows the use of elements of separate chimneys from the Protherm chimney catalog for wall-mounted boilers.

The maximum flue length is 10 equivalent meters (1 equivalent meter = 1 meter straight section or one 90 ° elbow).

A warning:

When using the PROTHERM PT 20 (30, 40, 50) fan extension, the terminals of the flue gas thermostat must be bridged before the boiler is started up. In this mode of operation, the air manostat, which is included in the delivery set of the PT 20 (30-50) chimney extension, acts as a safety element. Only a specialist from a specialized organization certified by Protherm may install and operate the boiler extension.

When performing service work while the extension is connected to the power supply (even with the mains switch turned off), the safety instructions must be observed!

It is convenient to monitor the deviation from the initial water pressure in the heating system using the pressure gauge on the boiler control panel using the red arrow of the pressure gauge. If the pressure in the heating system drops, locate and eliminate leaks or bleed air from the heating system or check the expansion vessel.

The expansion tank of the boiler must be adjusted depending on the parameters of the heating system - in this way, the heating system and all its elements during operation are protected from unwanted load during sudden changes in pressure.

When filling the built-in DHW boiler, it is necessary to open the cold water supply line to the boiler and the DHW outlet line from the boiler. As soon as water starts to come out of the DHW line, this will mean that the boiler is completely filled with water.

Note:

In front of the boiler (i.e. on

return line of the heating system) it is recommended to install a sump for slag from the heating system. The sump can be combined with a sump, it must have shut-off service valves.

Comments (1)

Highlight → I found instructions for my water heater here! #manualza

  • Click →

Instruction: “It is forbidden to disassemble the device. There are no parts that can be repaired by the user. ” The manufacturer intrigued me. Practically provoking!

Manualza! Manualza.ru

Still not with us?

How does Proterm Cheetah work when connecting thermostats?

When the gas boiler Protrem Cheetah is working without room thermostat, space heating depends on the temperature setting of the heating medium.

When connected to a gas boiler Proterm thermostat it becomes possible to set the desired heating temperature. It must be such that the unit can support it, regardless of the outside temperature. The regulator will only control heating within the selected range.
Note! In the room where the room regulator is located, the radiators cannot be equipped with thermostatic valves.
Unit Proterm with two-position regulator able to maintain the set heating temperature. The boiler will receive a signal to switch on or off depending on the temperature in the room in which the regulator is located.

When connected to a gas appliance continuous regulator the power will change smoothly to maintain the set room temperature.

The room regulator will control the room temperature and send a signal to the unit to turn off if the heat level reaches the set one or turn on if the temperature decreases.

cauldron wipe cheetah

The most modern and accurate is equithermal regulation... It is performed by a thermostat with an outside temperature sensor. When such a device is connected to a gas boiler, the latter will regulate the temperature of the coolant, depending on the conditions outside.

If the operation of the unit is controlled by an equithermal regulator, it is not recommended to set the maximum temperature of the coolant - this will significantly reduce the efficiency of the system.

Find out here how to make a gas boiler more economical?

Malfunctions of gas boilers Proterm and their elimination

Features of ignition of different models of gas boilers

Setting up a gas boiler Proterm Medved

The floor-standing gas boiler Proterm Medved has a simple design. There are models on sale that can only provide heating, and there are those that produce hot water. Depending on the characteristics, the Proterm Medved gas boiler is configured as follows:

  1. DHW temperature - press the MODE button, the lamp in the upper left corner will start blinking, and another diode will be on in the lower right. Using the button with the image of two arrows pointing upwards, set the required temperature in the boiler in the range of 40-70ºC. Confirm the selected temperature by pressing the MODE button.
  2. Heat carrier temperature - in the heating temperature setting mode, the lamp blinks in the upper left corner. Using the button with two arrows pointing up, set the required temperature of the heat carrier in the range of 45-85ºC. Press the MODE button to activate the selected value.

The temperature list contains the parameter -. When it is selected, the gas boiler switches to summer mode, when the heating is turned off and the hot water supply mode is working.

proterm bear settings panel

When an equithermal temperature regulator is connected to the boiler, additional settings are made.

We eliminate breakdowns on the Protherm KLOM boiler

_______________________________________________________________________________

_______________________________________________________________________________

Gas boiler Proterm 40 KLOM cannot start. As long as you hold the start button, the burner is in operation. But if you do not fix the button, the device starts to go out. What is the cause of the malfunction? The thermocouple or gas valve may be out of order. Low gas pressure in the supply line may also occur. Sometimes there is insufficient voltage on the control board. There is a problem. The start is difficult. The pilot burner is on, but there is no flame on the main burner. I just can't understand what is the reason? Possible damage to parts of the ignition unit. It is necessary to carry out service maintenance of the device and cleaning of the igniter. What is the problem if the floor-standing single-circuit boiler Protherm Bear 30 KLOM stops turning off the moment it reaches the required temperature? Heating continues up to 90 degrees, after which it goes into an accident. After a reboot, the situation repeats. Probably, the board is out of order, the boiler water temperature sensor is damaged, the overheating sensor is broken. It is possible that there was a malfunction in the automation. I would like to know why the boiler does not heat above 70 C? I need to set more, and the screen shows that this is the maximum value. How can the heating be increased? If the appliance cannot complete the cycle of increasing the temperature in the heating system, then the following reasons are possible. In the given adjustments, the maximum heating temperature is set to 70 C. The draft in the chimney channel has decreased. Single-circuit boiler Proterm 20 KLOM unstably performs functions in the heating mode of the DHW circuit. Hot and cold water is pouring from the tap. Tell me what the reason could be? The reasons for the appearance of a functional failure are possible as follows. There is a mixture of cold water due to the fact that the 3-way valve is inoperative. Heat exchanger very dirty.You should clean it up. There is a tap under the boiler and water drips from it regularly. The unit itself does not start. What to do? Obviously, there is a coolant discharge from the safety valve. In this case, this indicates an increased pressure in the system. Also, the make-up valve of the system might not be closed or it was required to pump the expander tank. Please tell me why there is a constant increase in pressure, and also the water relief valve starts to work? The display shows a constant heating icon when the appliance heats up. How to be? There is a problem with the temperature sensor in the heating circuit. There is no normal circulation in the heating line. Why did the Protherm Medved 40 KLOM gas boiler often turn off? Let's say the other day the piezo ignition did not function at all. The unit was serviced a month ago. What's the matter? We assume that there are problems in the smoke extraction process. You need to inspect the chimney. Incorrect operation of the ignition element will mean a defect in some component due to variable voltage or water ingress. Can anyone help solve the chimney problem? Soon for three days, as the return thrust is observed, because of which the smoke passes directly into the room. The chimney was made by myself. It consists of a metal tube. It looks like there is an error in the calculations. The unit perfectly performs DHW heating, but when you turn on the heating, the water quickly boils, and the unit turns off. What is the problem and how can I get rid of it? Most likely, the circulation pump is not working, the control board has failed, the temperature sensor is broken. At the same time, the filter mesh may become dirty. In the DHW cycle, the boiler alternately starts to dispense hot and cold water. It is not clear what it depends on. How to set up water heating? Apparently, there is dirt in the heating system or the heat exchanger needs cleaning. There may also be a malfunction of the flow switch or a damaged circulation pump. An important reason may be the incorrect configuration of the chimney. Sometimes there is a deposit of soot on the walls of the pipe, which sufficiently weakens its efficiency. In addition, it is advisable to inspect the ventilation in the room. We operate the floor-standing boiler Proterm Medved 50 KLOM. The device quickly raises the temperature to 96 C, and then it is blocked by overheating. Later, when it cools down, it can turn on on its own. What is the reason for this? An overheating alarm indicates a circulation problem in the system. Beforehand, you need to control the position of the heating radiator taps. They need to be opened. Then a check is carried out for the cleanliness of the filter element, and it is also recommended to make sure that the heat exchanger does not contain any dirt. I commissioned this boiler in March. About six months later, the device suddenly began to make a lot of noise. Explain why there is noise in the boiler? The heat exchanger may be clogged with limescale. If the water is hard, limescale deposits will subsequently build up in the radiator pipes. We are thinking of connecting a floor-standing gas boiler Protherm KLOM 17 to the heating system. I would like to know how it is unmistakably recommended to start it up? For the correct commissioning of this equipment, certain procedures are required. We turn on the power supply to the device. We put the gas valve open. Then we turn on the main burner. Finally, we adjust the desired temperature. We want to carry out service. Instruct on how to drain the unit yourself? According to the manual, this operation is performed in the following order. Disconnect the device from the power supply. Close the gas cock. We slightly open the automatic air vent. Open the drain valve completely. Next, we collect the leaked liquid. It is also allowed to drain the water through the safety valve. This valve is located at the bottom of the apparatus.Explain to me how to check the function of a 3-way valve? There is a suspicion that he does not complete the opening until it stops. In the heating cycle, it does not pump the last batteries, however, in the hot water supply mode, the pipe is very hot for the heating supply under the boiler unit. It is of course necessary to check the 3-way valve for stem sticking in an intermediate position. In turn, we recommend that you carry out an inspection of your heating system. We operate at the Proterm Medved dacha 30 KLOM. Worked smoothly until yesterday. At the moment, after five seconds after the start, the device began to go out. There is an assumption that it cannot deliver the coolant to the system. Tell me what is the reason? A possible cause of this damage can be the ignition electrode, which does not detect the fire, or a decrease in circulation. Just yesterday we had a malfunction with this unit. In heating mode, it whistles. I tried to restart it - I succeeded, but the whistle does not disappear. Maybe someone will tell you what is the reason for the whistle? In many cases, a loud whistle occurs when the pressure on the nozzles of the gas burner is incorrectly set. It is necessary to check the established indicator and correct it if necessary. Water was recently poured into the boiler, and the device began to malfunction. For example, if you set an arbitrary temperature, and the heating reaches from strength to 22 degrees, and then the device turns off. Tell me what is the problem? If an electronic board unit has been flooded with water, it can be assumed that the circuit board has deteriorated. We recommend that you carry out its zeroing by directly disconnecting the device from the power supply. After that, turn it on again and diagnose its serviceability. We put into operation a gas boiler Protherm 50 KLOM. Today, during the start, the wick burns for 8 seconds, and the main burner does not catch fire, so the unit goes out. How can you fix the breakage? Based on your words, the automatic ignition has broken or there is a problem with the burner. Just in case, check if the phasing is not broken at the time of connecting to the mains. I carried out the launch of the same model myself at the beginning of August. Approximately five months later, the DHW circuit stopped working, while in heating mode it functions smoothly. I tried to open the hot water tap, but it only indicates the temperature, and is not going to produce heating. Tell me what is the reason? It can be assumed that there is a breakage of the three-way valve. It needs to be replaced. Tell me, for which functions is the boiler equipped with a safety temperature sensor? The temperature sensor stops the gas supply to the burner in case of overheating of the liquid in the primary heat exchanger. I was advised to wash and clean the primary heat exchanger. Explain how to properly disconnect it? The heat exchanger can be easily removed from the boiler unit using a standard screwdriver. Below is a description of the dismantling procedure. We drain the water from the unit using the drain valve. Then we free the hot water system from the water. Unscrew the securing bolts of the primary heat exchanger and pull it out of the frame. I started with this unit. After about six months, the water pressure in the device dropped. Sometimes it resets it and shuts down. That is, he cannot hold the pressure at all. What could be wrong? When the device does not gain water pressure, it can be assumed that the make-up tap is leaking. When the shutdown occurred and the pressure dropped to zero, the 3-way valve broke. Tell me how to clean the cold water filter? The initial stage is to drain the water from the DHW circuit. Secondly, unscrew the flow sensor nut. Next, dismantle the sensor together with the filter from the socket. After that, we clean the accumulated impurities and dirt. The device buzzed earlier during the start-up period, but at this time it is louder. Initially, the sound was not heard for long, but now it lasts much longer.arose for a short time, faced such a problem? Excessive noise indicates the presence of limescale inside the heat exchanger casing, which heats up unevenly due to different wall thicknesses. The more dirty the heat exchanger is, the more pronounced the noise is, which reduces the heat output. The unit is running, although there is clearly no water circulating in the system. The return pump heats up noticeably. Why is heating happening? Apparently, the filter is dirty or the tap is closed somewhere, which blocks the movement of the coolant. The circulation pump may also break. Why does hot water stop heating? The tap water is very warm. Can you explain what happened? Damage search is conducted in several directions. For example, there is a problem with the hot water temperature sensor, you need to replace it. There is also a possibility that the setting of the power of the device for heating the water has gone astray. From time to time I observe the termination of the spark at the moment of ignition. The burner is clean, everything is normal with the chimney, there are no problems with draft. Where can I find the problem? The device cannot detect the flame due to insufficient notification from the combustion control unit. Here you need to check the wiring between the ionization sensor and the electrode. Obviously, it should be tightened. There may be a defect in the insulation of the sensor and must be replaced.

_______________________________________________________________________________

_______________________________________________________________________________

  • Gas boilers
  • Electric boilers
  • Boiler error codes
  • Elimination of malfunctions in boilers
  • Gas water heaters
  • Malfunctions and repair of gas water heaters
  • Water heaters
  • Troubleshooting water heaters
  • Repair of indirect heating boilers
  • Elimination of malfunctions in electric convectors

_______________________________________________________________________________

  • BAXI ECO FOUR

Heating system control. Installation. Connection. Transfer to another type of gas. Adjustment devices and protection devices.

  • BAXI LUNA

Features. Installation and assembly. Automation components.

  • BAXI MAIN FOUR

Technical specifications. Installation. Adjustment and check. Maintenance.

  • BAXI SLIM

Regulation and protection. Installation and assembly. Pressure setting. Maintenance.

_______________________________________________________________________________

_______________________________________________________________________________

  • BAXI - REPAIR

After starting, a malfunction appeared. He does not want to turn on, he worked for two years, now the entire display is on fire as if the boiler is turned on, when the self-diagnosis mode is on, then it clicks, turns off for miles and then turns on the entire display again. It turned on once, but gives an error E10 water pressure, although the pressure in the system is 1.5 atm. Tell me what could be?

  • BAXI - OPERATION

In operation, the Baxi main four 240 boiler is turned off with an E35 error (parasitic flame). Tell me what to do? The first season is in operation.

  • BAXI - SETTINGS

We installed and connected a Baxi Fourtech 24 F boiler. What cold water pressure is allowed at the inlet to the DHW device?

  • BOSCH - REPAIR

Bosch 6000 boiler 24 kW, single-circuit with a built-in three-way valve. Does not see the boiler sensor, gives an error. Tell me how to make sure that it does not give an error and work normally both for heating and for a boiler?

  • BOSCH - ADJUSTMENTS

If you disable the DHW flow sensor, can it be possible to reprogram it into a single-circuit device through the L3 menu?

  • ARDERIA - REPAIR

Installed the Arderia esr 2.13 ffcd boiler. If my coolant pressure drops a little in 2-3 days for a couple of divisions, can there be a reason for the malfunction of the three-way valve (there are no leaks from the radiators)?

  • ARDERIA - ADJUSTMENTS

The gas boiler Arderia is in operation 2.35. Tell me about the power reduction. I heard something about modulation, fan speed and so on. Is it possible to really reduce the power?

_______________________________________________________________________________

  • BUDERUS FLOOR

We installed and connected a Buderus Logano G234-WS-44 kW boiler, Logomatic 4211 automatic equipment. Heating on cylinders without hot water supply, nozzles for reduced gas were also replaced. We survived the winter, the cylinders were replaced, all without problems.Then in the spring, when the temperature outside is + 16 + 18, the boiler began to turn off for a long time and when turned on, it began to display a burner error on the screen and a red button light on the front wall lit up. We pressed the button, turned on the power again and everything worked. It happened several times, then for the summer they turned off the boiler completely, what could be the malfunction?

  • BUDERUS WALL

In a single-circuit Buderus 072, is the BKN coil circuit heated by the same heat exchanger as for heating or the same as on the 2-circuit one that is on the DHW?

  • VAILLANT - REPAIR

Tell me, for Vaillant wall-mounted gas boilers, are there real / actual differences for the better in the new generation of turboTEC plus VU / 5-5 compared to / 3-5?

  • VAILLANT - ADJUSTMENTS

Malfunction in the operation of the boiler, the green LED (power supply) flashes, the instructions say that the thermal protection has worked, the green indicator flashes, even if nothing is connected to the board. How to fix? I checked all SMD resistors and transistors, everything is in order.

  • DAEWOO

A double-circuit gas boiler Daewoo Gasboiler with an electronic panel is in operation. When the DHW is turned on, the heating is heated, the operating mode is summer. I took off the three-way valve, there is no dirt and production. It seems that the board does not control the three-way valve. How to check?

  • ELECTROLUX

The wall-mounted boiler Electrolux Basic Xi ​​is installed and connected. A malfunction began that the boiler stopped seeing the flame and turned off the gas supply after 7-8 seconds. And after 3 attempts, it gave an E1 error. How can you fix it?

  • KOREA STAR

Malfunction of the Koreastar boiler. The heating works perfectly, hot water is intermittent, when the hot water tap is turned on, cold water comes first, then boiling water. After a few seconds, cool, then boiling water again. What could be the problem?

  • FERROLI

Malfunction of the ferroli domiproject 24 boiler - I adjust 60-70 degrees, it goes to minimum combustion, does not turn on, does not turn off. Restarting is unstable. No pattern is revealed. What to do?

  • JUNKERS

In operation, the gas boiler Junkers euroline, when hot water is turned on, ignites the gas, then goes out and so on several times. If you turn it on while the heating is running, then the water heating turns on immediately. Can you please tell me what could be the problem?

  • NAVIEN

Tell me about the adjustments of the gas boiler Navien Ace 16 turbo remote control v1.3. Cannot set the fan run-down. I bet 30 seconds, but still 2 minutes. twists.

  • OASIS

Malfunction of the boiler Oasis ZRT18. The unit starts up, the gas is ignited, then it goes out. It lights up again, goes out (three times it happens). Then it flares up and works fine. It does not give any error. What is the reason?

  • SAUNIER DUVAL

Malfunction of the gas boiler Senor Duval - the water pressure sensor shows 0.0, the indicator flashes red, hot water does not heat up, but the water pressure in the apartment is good. How do I fix the problem?

  • VIESSMANN

Where should the condensate drain be installed in the coaxial flue? Boiler wh1d with a closed combustion chamber, located at a distance of 1m from the wall.

  • WESTEN

The problem of starting the Westen Pulsar D boiler. Piezo ignition works, but there is no flame, after a crackling error E01. Rearranged the fork in places.

  • BERETTA

The Novella floor-standing gas boiler has blocked - the green lights on the panel are on, and nothing else happens. How to fix?

  • ARISTON

An Ariston gas wall-mounted boiler was installed and connected, which does not hold pressure at all: during the cooling of heated water, the pressure drops to zero, although water is regularly drawn. What's with the pressure?

  • SIME

Malfunction of the metropolis dgt 25 bf boiler. The hot water supply stopped working, the heating is working, it does not give an error. What do you advise?

  • SOLLY

Please tell me how to solve the problem. The Solly Standard boiler, with any attempt to turn it on or hot water, gives a GS error.

  • WOLF

The Wolf boiler is in operation. Recently, he began to behave strangely: in the pause between starts, he turns on the burner for one second five times, and 70 degrees jumps out on the display. Where to look for a malfunction?

  • ACV

ACV Wester Line works very unstable: it often goes into an accident, emits a characteristic knock at startup and stalls, and at times everything is fine. The unit is almost new, what's wrong with it?

  • DEMRAD

In the gas boiler Demrad, gas is no longer supplied to the burner. The piezo element clicks, but there is no ignition. Everything is in order with the gas stove, there is gas. What is the reason?

  • KITURAMI

Malfunction of the Kiturami world boiler, stops periodically. I wipe the flame sensor and the apparatus works well for a while, but soon everything repeats itself. He also began to smoke heavily. Maybe it's a short chimney, and you need to lengthen it?

_____________________________________________________________

  • IMMERGAS - ERRORS

Errors of boilers Nike Star, Eolo Star / Mini, Mythos. Boiler malfunctions with the ability to automatically unlock.

  • IMMERGAZ - REPAIR

My boiler in winter mode systematically raises the temperature to 80 degrees. He summoned the master three times. He said that this is for many imergaz models, and offered to install a programmer, but not the fact that it would help. Tell me how to solve this problem and will this programmer help?

  • AOGV

Model 11.6; 17.4; 23.2; 29.3 kW. Specifications. Control elements of the automation unit. Installation and maintenance. Malfunctions and their elimination.

  • AOGV - REPAIR

The gas boiler AOGV was installed and put into operation. Hot water dispensing problem. The heat exchanger has been flushed. Less than a month has passed, and the water does not flow again. We put the filter on the water, but time has passed, and again hot water does not flow. What could be the breakdown?

  • AGV

Assembly and installation. Start-up and adjustment. Malfunctions and ways to eliminate them.

  • AKGV

Technical specifications. Installation and connections. Startup and work order. Automation adjustments.

  • NEVA LUX

Malfunction of the boiler Neva lux 7023. With a frequency of 2 times a month, it gives an error E7. But after a reboot it still works. Now it gives an error E6. It will work for 15 minutes, and then it turns off. What could it be?

  • ROSS

Construction and automation unit. Firing up procedure. Malfunctions and repairs.

  • ATEM ZHITOMIR

Tell me if the Atem Zhitomir boiler goes out because of the weak gas pressure, it clicks and goes out. What is the problem? Is it possible to turn off the automation for a while and how?

  • LEMAX

A gas boiler Lemax KSG-12.5 Premium was installed. After turning off the main burner, a click occurs after a couple of minutes, what is the reason, tell me?

  • KEBER

A gas boiler KS-G was installed and connected, for 250 sq. m. When firing up, it does not turn off, the temperature rises, if I am not mistaken, the automatic Arbat 1. The flame is not regulated - too large. What to do?

  • LIGHTHOUSE

I installed a gas boiler Mayak and connected it. It works fine. But the reason is this. When it works on a unit, it beeps strongly, if the regulator is turned 2-7, the squeak disappears. Tell me what could be?

  • DANKO

We installed and connected the Danko gas boiler with the Kare automatics, it works fine on the igniter, but it is worth adding the power on the burner, it completely fades, yesterday it faded out for 5 minutes, today it works for 20 minutes and completely goes out. Who faced this problem?

  • GAZLUX

The boiler gazeko 18 is in operation. When hot water is turned on, the pressure in the system drops after make-up, the pressure reaches 3 bar. Have to dump. What's the matter, how to fix it?

  • NOVA FLORIDA

Water often boils in the boiler, while it goes into an overheating accident. The heat exchanger was recently washed, the system is not clogged. What's the matter?

  • RINNAI

Malfunction of the Rinnai 167 RMF boiler. Recently started showing error 14. How can you fix the breakage?

  • CELTIC

The Celtic ds boiler heats up to 45 degrees and costs the whole day it does not turn off and does not heat up the batteries, sometimes it shows an a3 error. How can this problem be resolved?

  • MORA

The hot water pressure in the Mora Top boiler has dropped. What is the reason?

  • MASTER GAS SEOUL

Seoul wall mounted gas boiler stopped turning on due to no ignition error. How can it be eliminated? What exactly is out of order?

Boilers

Ovens

Plastic windows